Ascent Petrochem Holdings Co., Limited
Articles
Articles

Articles

Sheet Metal Deep Drawing Compound Dilution and EP Additive Solvency

Sheet metal deep drawing compounds based on high-viscosity mineral oil, calcium sulfonate, polymeric esters, and bound long-chain fatty acid soaps are often supplied at kinematic viscosity of 400–1,200 mm²/s at 40°C when measured under ISO 3104:2023 or ASTM D445-21. Dilution is required whenever the application hardware—airless spray, air-assisted spray, or high-speed roll coater—cannot generate a stable film above a working viscosity ceiling. Airless spray nozzles with 0.011–0.015 in. tungsten carbide orifices and 6.9–10.3 MPa inlet pressure typically deliver acceptable fan patterns only when the diluted compound is maintained between 18 and 45 mm²/s at 40°C, according to manufacturer technical bulletins for piston-pump electrostatic and conventional systems. A paste with an as-supplied viscosity of 800 mm²/s therefore requires roughly 3:1 to 5:1 volume dilution with a solvent having a flash point above 38°C and a distillation end point below 200°C to remain feasible under ASTM D93-20 Pensky-Martens closed-cup flash point criteria for plant handling. The solvent also must prevent precipitation of the extreme-pressure package. Chlorinated paraffins in the C14–C17 chain range with 40–52 wt% chlorine exhibit limited solubility in high-aniline point aliphatic solvents; a solvent with a kauri-butanol value of 33–38 per ASTM D1133 and an aniline point of 60–75°C per ASTM D611 is commonly selected to maintain additive solvency at plant floor temperatures down to 10°C. Production experience on transfer presses with central circulating lubricant reservoirs indicates that batch-to-batch viscosity drift of ±5% in open mixing tanks, caused by evaporative loss of light solvent ends, produces measurable shifts in spray droplet size distribution, with a 3 mm²/s increase at 40°C moving the volume median diameter from approximately 35 µm to 60 µm and creating local starved-film zones on the blankholder ring.

What Limits Solvent Dilution Before Extreme-Pressure Film Formation Collapses?

The load-carrying capacity of a diluted deep drawing compound is not a single property but a combined function of hydrodynamic film thickness, additive concentration at the tool-workpiece interface, and the solvency state of the EP additive. Dilution reduces viscosity and therefore the hydrodynamic film thickness generated in the inlet zone of the drawing gap. At the same time, dilution reduces the concentration of active sulfur, chlorine, or phosphorus available to form a sacrificial reaction film when asperity contact occurs. The boundary lubrication regime is evaluated under ASTM D3233 Method A using a Falex pin and vee block apparatus where a steel journal rotates at 290 rpm against two hardened steel V-blocks under incrementally increasing load; failure is recorded as seizure or torque rise. In four-ball testing to ASTM D2783, the weld load of an undiluted drawing paste may be several load stages higher than the same paste diluted 50% with a low-solvency isoparaffinic solvent, but published data for specific formulations is limited because additive response is not linearly proportional to dilution ratio. The failure load often collapses once dilution reduces the additive content below the threshold required to maintain a coherent antiweld film on the die radius. Sulfurized olefins require thermally activated reaction at local contact temperatures above 200–300°C; if the solvent evaporates too quickly, the residual film is too thin to carry the additive to the reaction site, while if the solvent is too high-boiling, the additive remains solvated and cannot partition to the metal surface. This solvency-reactivity conflict is the main limitation on dilution ratio. A low-aromatic hydrotreated naphtha with 10–20% aromatic content and a distillation range of 150–200°C per ASTM D86 offers a compromise: it evaporates quickly enough to leave a concentrated additive film at the die interface but retains enough solvency to avoid additive precipitation in the spray line. The dilution ceiling for high-chlorine formulations is commonly set at 20–30 wt% solvent when the neat compound is 400–800 mm²/s at 40°C; beyond that point, Falex seizure load per ASTM D3233 may drop below the minimum acceptable for deep drawing HSLA steel of 1.5 mm gauge, though exact thresholds must be verified by formulation-specific testing.

Solvent classes and solvency indicators relevant to EP additive stability
Solvent typeKB value per ASTM D1133Aniline point per ASTM D611 (°C)Aromatic content (wt%)Typical solvency behavior for chlorinated paraffin packages
Hydrotreated light naphtha33–3860–75<1–2Stable at 10–15°C with 40–52 wt% chlorine paraffins
Stoddard solvent35–4560–7510–18Higher solvency reserve but slower evaporation
Isoparaffinic solvent25–2975–85<0.1Risk of additive precipitation below 20°C
Aromatic 10090–10012–20>99Excellent solvency but VOC and resin swelling limitations

Because roll coating equipment operates at wet film thicknesses of 2–8 µm and deposition weights of 1–3 g/m², the solvent balance must prevent both strike-through and dry-film starvation. In a typical steel service center leveling and blanking line, a polyurethane roll coater applies diluted compound to both sides of cold-rolled or hot-rolled pickled and oiled steel. The dilution ratio is usually 10–20 wt% with a hydrotreated light naphtha having a flash point above 40°C and a KB value above 33. If the solvent is too strong, it can swell the polyurethane rolls, causing durometer change and crown loss; roll hardness is maintained between 25 and 40 Shore A for uniform transfer. If the solvent is too weak, chlorinated paraffin and overbased calcium sulfonate can settle in the engraved metering roll cells, producing a starved transfer pattern that appears as longitudinal dry streaks on the sheet. The most common field failure in this application is not additive decomposition but additive sloughing: the diluted compound forms a clear solvent-rich supernatant over a dense additive-rich bottom layer in open 55-gallon drums stored at ambient temperature. A 10 µm absolute filter in the recirculation loop then plugs within 4–8 hours of operation, a failure mode reported in central systems supplying multiple roll coaters. Preventative control is based on maintaining the aniline point of the solvent blend below 75°C and avoiding dilution with isoparaffinic solvents that have KB values below 28.

When Low-Aromatic Hydrotreated Naphtha Replaces Stoddard Solvent in Paste Dilution

Substitution of Stoddard solvent with low-aromatic hydrotreated naphtha is driven by VOC reduction and worker exposure limits under EU Directive 2004/37/EC or REACH restrictions on benzene and naphthalene, but the change alters EP additive solvency in ways that are not captured by viscosity alone. Stoddard solvent typically has an aromatic content of 10–18 wt%, a KB value of 35–45, and an aniline point of 60–75°C; low-aromatic hydrotreated naphtha may have aromatic content below 2 wt%, KB value of 30–35, and aniline point of 65–75°C. The loss of aromatic character reduces the solvency reserve for chlorinated paraffins, especially at winter storage temperatures below 15°C. A chlorinated paraffin of 52 wt% chlorine and chain length C14–C17 can remain dissolved in a 35 KB solvent at 20°C but may separate as a hazy floc when the same blend is stored overnight at 5°C. This phase separation is reversible upon warming and agitation, but production facilities rarely have heated storage for diluted drawing compounds. The practical consequence is that low-aromatic substitution often requires reformulation of the additive package: replacing chlorinated paraffin with sulfurized fatty esters or phosphate esters that have higher polar solubility, or adding a small amount of ester co-solvent such as 2–5 wt% of a branched C8–C10 ester coupling agent. The ester co-solvent raises the KB value and lowers the aniline point without exceeding the flash point limitations of ASTM D93-20. When a solvent substitution is made without such reformulation, the first observed failure is usually filter pressure rise in the airless spray recirculation line, followed by lowered Falex seizure load under ASTM D3233 because the chlorinated additive is no longer delivered uniformly to the die interface.

Manual brush application of zinc phosphate coated steel does not require the same degree of dilution as spray application, and the solvency trade-off shifts toward slower evaporation and longer open time. A paste diluted 5–10 wt% with Stoddard solvent retains a viscosity of 200–400 mm²/s at 40°C under ISO 3104:2023, which is brushable but still forms a thick film on phosphate crystals. The EP additive solvency is less strained because the solvent concentration is low; however, the solvent must remain in the film long enough to soften the paste and allow it to flow into phosphate microporosity. If a low-boiling VM&P naphtha is substituted to reduce drying time, the film can skin over within 2–3 minutes on a warm blank, trapping solvent and preventing uniform additive distribution. The trapped solvent later vaporizes during the first draw, creating a localized gas phase that disrupts the boundary film and produces scoring on the die radius. A solvent with an initial boiling point above 150°C and a dry point below 210°C per ASTM D86 is generally retained long enough to maintain additive mobility, while still evaporating before the formed panel enters a subsequent cleaning stage. This application also illustrates the difference between additive solvency and additive mobility: a solvent can dissolve the EP package in the drum but fail to release it at the metal surface if the solvent flash point is too high and the wet film remains solvated into the draw zone.

Thermal Degradation Pathways in Chlorinated Paraffin-Catalyzed Systems

Chlorinated paraffins function as extreme-pressure additives by decomposing at freshly exposed metal surfaces under frictional heat, releasing hydrogen chloride and forming a metal chloride film with low shear strength. The decomposition onset for commercial chlorinated paraffins in the C14–C17 range is commonly reported between 160°C and 220°C, but the local flash temperature at a die radius during deep drawing of stainless steel can exceed 400°C for short intervals. In a heavily diluted compound, the thermal activation threshold is reached only after solvent evaporation; if the solvent is high-boiling, the endothermic evaporation front can delay additive activation until the blank has already passed the critical drawing zone. This delay is observable in progressive die trials as galling on the lower die radius, not because the additive is absent, but because it remains solvated and unable to react with the metal surface. The degradation products of chlorinated paraffins include hydrogen chloride, which can cause corrosion of tool steel if not neutralized by the overbased calcium sulfonate reserve of the compound. A compound diluted too aggressively may have its alkalinity reserve reduced disproportionately because the solvent does not carry overbased detergent packages uniformly. The copper strip corrosion test per ASTM D130-19 is used to detect active sulfur or HCl-related corrosion; a result above 1b in the as-diluted fluid indicates a risk of staining or pitting on copper-containing tool components. Amine-based corrosion inhibitors should not be added to chlorinated paraffin-containing compounds without specific compatibility testing because amine hydrochloride salt formation can deplete the active chlorine and increase corrosive by-product formation. In stamping plants using epoxy-coated dies or laser-welded blanks, the presence of chlorinated paraffin degradation products can interfere with subsequent adhesive bonding; the residue must be removed by alkaline cleaning at 60–80°C with a pH of 9–11 using surface cleanliness assessment principles per ISO 8502-3. Published data on the exact decomposition kinetics in diluted forming compounds is limited; however, the thermal stability of chlorinated paraffins is routinely characterized by thermogravimetric analysis under nitrogen and by differential scanning calorimetry, not by a single standardized test.

Progressive die lubrication on high-strength steel requires solvent evaporation rate to be matched to stroke rate and die temperature; a solvent that evaporates too quickly chills the die surface and condenses moisture, whereas a solvent that leaves a wet film can cause adhesive transfer in the die cavity. Coating systems using high-speed rotary atomizers set the dilution ratio to achieve viscosity of 15–25 mm²/s at 40°C under ISO 3104:2023, but the solvent must have a flash point above 55°C and a relative evaporation rate below 0.3 relative to n-butyl acetate per ASTM D3539. The use of low-flash blends to increase evaporation rate violates closed-cup flash point classifications under ASTM D93-20 and creates a fire risk in enclosed press pits where solvent vapor accumulates. In high-volume lines producing automotive body panels, the diluted compound is typically circulated through a temperature-controlled header at 20–25°C to prevent both solvent evaporation and additive precipitation. If the header temperature is raised to 35°C to reduce viscosity, the vapor pressure of the solvent rises and the concentration of active EP additive delivered per stroke falls because the solvent flash evaporates before the sheet enters the die. The practical control range for these systems is tight: viscosity variation greater than ±2 mm²/s at 40°C across the header manifold can produce visible banding on the formed panel surface, a defect that is often misdiagnosed as tool misalignment but is in fact a fluid delivery asymmetry.

Roller Leveler and Blank Washer Compatibility with Chlorinated Additive Residue

Blank washers operating before press feed must remove chlorinated additive residues without destabilizing the drawing compound that is reapplied downstream. Solvent dilution affects residue behavior because a poorly solvated chlorinated paraffin forms a tenacious, gelled film on the metal surface that resists alkaline wash chemistry. In a typical washer, the blank passes through staged immersion and spray zones with alkaline cleaner at 60–80°C and 1.0–2.0 MPa spray pressure; the cleaner chemistry is formulated to saponify fatty esters and emulsify mineral oil, but chlorinated paraffin degradation products require higher alkalinity and longer contact time. If the drawing compound was diluted with an isoparaffinic solvent of KB value below 28, the chlorinated additive may have already precipitated as a particulate film on the sheet, making removal more difficult and increasing the load on the washer’s coalescing filtration system. Field observations indicate that washer bath life can be reduced by 30–50% when feedstock blanks carry precipitated chlorinated additive rather than a uniform oiled film, though published data for this specific configuration is limited. The choice of solvent therefore influences not only drawing performance but also the downstream cleaning operation and the long-term stability of the drawing compound in the press pit. Chlorinated paraffin residues are also controlled under REACH because medium-chain chlorinated paraffins are classified as SVHC; formulators increasingly replace them with polymeric ester and overbased calcium sulfonate combinations that do not require high aromatic solvency. The compatibility of recycled cleaning solution with the fresh diluted compound should be checked by measuring acid number per ASTM D974 and copper strip corrosion per ASTM D130-19; acid number above 2.0 mg KOH/g indicates carryover of chlorinated degradation products or cleaner drag-in that can destabilize the oil phase.

Test methods and typical control ranges for solvent-diluted deep drawing compounds
PropertyStandardControl range or limitRelevance to EP additive solvency
Kinematic viscosity at 40°CISO 3104:2023 / ASTM D445-2118–45 mm²/s for airless spray; 200–400 mm²/s for brushControls film thickness and additive delivery
Kauri-butanol valueASTM D1133≥33 for chlorinated paraffin packagesSolvency reserve for polar EP additives
Aniline pointASTM D611≤75°CIndicates aromatic solvency; lower value improves chlorinated paraffin solubility
Flash pointASTM D93-20≥38°C plant handling; ≥55°C enclosed pressFire safety and solvent retention
Distillation rangeASTM D86IBP ≥150°C; dry point ≤210°C for brush applicationEvaporation rate and film open time
Falex seizure loadASTM D3233Formulation-specificDirect EP film strength under boundary lubrication
Four-ball weld loadASTM D2783Comparative onlyEP additive response after dilution
Copper strip corrosionASTM D130-19≤1bDetects active sulfur or HCl-related corrosion
Acid numberASTM D974≤2.0 mg KOH/gMonitors cleaner carryover and chlorinated degradation products

In plants where solvent-diluted drawing compound is used in close proximity to water-diluted synthetic coolants, the solvency model changes from kauri-butanol value to emulsifier hydrophilic-lipophilic balance. A solvent-diluted paste that enters a synthetic coolant sump as tramp oil can flash-separate chlorinated paraffin and sulfurized fatty esters because the water phase immediately reduces the organic solvent strength; the precipitated additive then forms a sticky sludge that blocks chip screens, transfer pumps, and draining troughs. Compatibility testing per ASTM D3707 for oil-water emulsion storage stability and per ASTM D130-19 for copper strip corrosion is required before any common-depression washer or central filter system is operated with both fluids. This mixed-fluid scenario imposes an additional boundary on dilution: the as-diluted compound must remain single-phase when cooled to the lowest overnight shop temperature, typically 10–15°C, because any phase separation at the sump interface will be amplified by water contact and mechanical agitation.

Aluminum sheet drawing presents a different solvency boundary because chloride-containing EP additives can initiate staining and pitting under forming moisture. Chlorine-free formulations based on sulfurized fatty esters, phosphate esters, and high-molecular-weight polymeric esters require a solvent with higher polar solvency than chlorinated paraffin packages; a KB value of 40–50 and an aniline point below 60°C are often needed to keep phosphate ester derivatives dissolved at 10°C. A solvent that was acceptable for chlorinated paraffin at 33 KB can throw down phosphate ester platelets in the spray header, causing nozzle blockage. This scenario imposes a dilution ceiling of 10–15 wt% for heavy aluminum drawing pastes when a single solvent is used, because higher dilution reduces the ester concentration and destabilizes the additive phase. At relative humidity above 60%, moisture ingress into ester-containing diluted compounds accelerates hydrolysis and acid number increase; air-conditioned storage is recommended for chlorine-free blends. Formulating a chlorine-free aluminum drawing compound therefore requires either a blended solvent system containing ester or aromatic co-solvent or a switch to water-based emulsion chemistry where the emulsifier hydrophilic-lipophilic balance controls additive transport.

Related Articles